'Honest and trustworthy, seeking truth from facts' is our company's ethical philosophy. In the tide of market economy, our company has always adhered to the business philosophy of ensuring quality, mutual benefit and win-win, and providing customers with high-quality Fixed Shell And Tube Heat Exchanger, hot water plate heat exchanger, lube oil cooler heat exchanger. We expect sincere cooperation and common development! We sincerely welcome domestic and foreign customers to visit our company, and maintain long-term contact and cooperation with us.
Thermal Heat Exchanger
Product Introduction
Thermal heat exchanger is a type of heat exchanger for heat transfer of two mediums with different temperature. It is suitable for two kinds of fluids and works best when two mediums are water (The terminal temperature difference can reach 1℃). Plate and frame heat exchanger is available in a large area of industries, from dairy industry to petrochemical industry, it's very common to see this equipment.


Material Design and Selections
For various applications and requirements, we provide many types of material.
Material Selection | ||
Plate Material | SUS304, SUS316L, SMO254, Ti, Ni, Hastelloy | ![]() |
| Gasket Material | NBR, HNBR, EPDM,Viton/Flurorubber,Chloroprene, Silicone Rubber | ![]() |
| Frame Material | Carbon Steel, Stainless Steel | ![]() |
| *For specific requirements, please contact us for confirmation | ||
Product Advantages
●Safety
●High heat transfer efficiency
●Small floor area
●Low fouling coefficient
●Convenient cleaning
What tests need to be completed before the HE leaves the factory?
The hydrostatic test should be done for the plate heat exchanger before use.
Steps:
1、Check whether the clamping size meets the nameplate requirements.
2、Prepare the blind plate and test pressure device, the pressure gauge can be installed on the test pressure device.
3、The air in the equipment should be fully discharged
4、According to the design pressure 1.25 times (or the nameplate given by the hydraulic test pressure) for a single side test pressure to determine whether there is leakage to the empty side of the plate heat exchanger. Hold pressure for 30 minutes without leakage for qualified.
5、The blind plate should be removed after the test.
mail: sales02@tranp.cn
whatsapp/phone: +86 18776369372
address: No.3 Waizi Factory, Xindun Village, Xintang Town, Zengcheng District, Guangzhou City, Guangdong Province, China
We adhere to the market-oriented, technology-centric, service-oriented policy, and the concept of achieving customers and creating value models to meet customer needs with various Best Price Heat Exchanger for Water Cooling Tower. Over the years, our company has built an innovative team which is eager to learn, dedicated and dare to be the first. Our corporate culture is to shape the brand and build the character. If you are looking for a supplier with good quality, fast delivery, excellent after-sale service, we will be your best choice.