We will ensure the effective implementation of various services, so as to improve the after-sales service and Diaphragm Pressure Vessel, bem heat exchanger, gas exchanger quality. Mainly do wholesale, so we have the most competitive price, but highest quality. We put product innovation in the first place, and excellence and ingenuity is our pursuit of each product. Based on a positive, enthusiastic, and refined corporate work attitude and the corporate spirit of 'honesty, responsibility, hard work, and dedication', our company has established long-term partnerships with customers.
Thermal Heat Exchanger
Product Introduction
Thermal heat exchanger is a type of heat exchanger for heat transfer of two mediums with different temperature. It is suitable for two kinds of fluids and works best when two mediums are water (The terminal temperature difference can reach 1℃). Plate and frame heat exchanger is available in a large area of industries, from dairy industry to petrochemical industry, it's very common to see this equipment.


Material Design and Selections
For various applications and requirements, we provide many types of material.
Material Selection | ||
Plate Material | SUS304, SUS316L, SMO254, Ti, Ni, Hastelloy | ![]() |
| Gasket Material | NBR, HNBR, EPDM,Viton/Flurorubber,Chloroprene, Silicone Rubber | ![]() |
| Frame Material | Carbon Steel, Stainless Steel | ![]() |
| *For specific requirements, please contact us for confirmation | ||
Product Advantages
●Safety
●High heat transfer efficiency
●Small floor area
●Low fouling coefficient
●Convenient cleaning
What tests need to be completed before the HE leaves the factory?
The hydrostatic test should be done for the plate heat exchanger before use.
Steps:
1、Check whether the clamping size meets the nameplate requirements.
2、Prepare the blind plate and test pressure device, the pressure gauge can be installed on the test pressure device.
3、The air in the equipment should be fully discharged
4、According to the design pressure 1.25 times (or the nameplate given by the hydraulic test pressure) for a single side test pressure to determine whether there is leakage to the empty side of the plate heat exchanger. Hold pressure for 30 minutes without leakage for qualified.
5、The blind plate should be removed after the test.
mail: sales02@tranp.cn
whatsapp/phone: +86 18776369372
address: No.3 Waizi Factory, Xindun Village, Xintang Town, Zengcheng District, Guangzhou City, Guangdong Province, China
We have many years of technology accumulation and strict quality management procedures to ensure the quality and performance of our Bitzer Plate Type Evaporator Condenser Fin Type Air Cooled Condenser. In an effort to meet your requires, be sure to seriously feel free to make contact with us. Over the past few years, tens of thousands of new and old customers have established cooperative relations with our company, and they have given a very high evaluation of our products and after-sales services.