Instantaneous air-source heat pump
+
  • Instantaneous air-source heat pump

Instantaneous air-source heat pump


Instant heating, with no temperature fluctuations.
The condensing operating condition is stable, with the COP consistently above 4.0, resulting in significant energy savings.
High defrosting efficiency and strong low-temperature performance.
Stable operation, longer compressor life, and low pump energy consumption.
Low long-term costs.

Category:

| Product Details

  • Instant heating, no temperature fluctuations.
  • The condensing operating conditions are stable, and the COP can be maintained above 4.0, resulting in significant energy savings.
  • High defrosting efficiency and strong low-temperature performance.
  • Stable operation, longer compressor life, and low pump energy consumption.
    Low long-term costs.
Model number TR-HP-HW11JTR-HP-HW19JTR-HP-HW22JTR-HP-HW26JTR-HP-HW38JTR-HP-HW45J
Power supply  380V/3N-/50Hz
Rated hot water output (L/h) 240 410 480 560 820 960 
Rated Heat Input (kW) 11.2 19.1 22.3 26.1 38.1 45 
Rated Power Consumption (kW) 2.8 4.6 5.6 6.5 9.5 11 
Winter hot water production (L/h) 150 255 290 340 500 590 
Heating Capacity in Winter (kW) 8 13.6 15.5 18.2 26.7 31.6 
Winter Power Consumption (kW) 2.65 4.3 5.2 6.1 8.9 10.5 
Maximum Operating Power (kW) 4 6.3 8 8.G12.5 16 
Maximum Operating Current (A) 8 12 15 17 24 30 
Rated hot water temperature CC 55 55 55 55 55 55 
Maximum hot water temperature CC 60 60 60 60 60 60 
Circulating water flow rate (m³/h) >2.3 >4 >4.6 >5.5 >8 >9.5
Cyclic takeover specifications 1 outer-threaded fitting 1-inch external thread 1-inch external thread 1.2-inch external thread 1.2-inch external thread 1.5-inch external thread
Water refill connection specification 1-inch external thread 1-inch external thread 1-inch external thread 1-inch external thread 1-inch external thread 1-inch external thread
Operating noise (dB) 63 70 70 70 75 75 
Appearance
    Size
Length (mm) 710 750 750 750 1450 1480 
Width (mm) 710 750 750 750 725 900 
Height (mm) 860 1060 1060 1060 1060 1650 
Weight (kg)  120 150 170 190 300 440 
  Quantity (units) 1 1 1 1 2 2 
Compressor Form Fully enclosed scroll type
Refrigerant R22 (optional R410a)
Wind turbine Quantity (units) 1 1 1 1 2 2 
Form Axial fan
Applicable Ambient Temperature Range (°C) -10~40℃
Model number TR-HP-HW53JTR-HP-HW77JTR-HP-HW93J TR-HP-HW110J TR-HP-HW150J TR-HP-HW180J 
Power supply  380V/3N-/50Hz
Rated hot water output (L/h) 1150 1650 2000 2350 3350 4050 
Rated Heat Input (kW) 53 77 93 109 150 181 
Rated Power Consumption (kW) 13 19 24 28 38 47 
Winter hot water production (L/h) 690 980 1200 1350 2000 2350 
Heating Capacity in Winter (kW) 37 52 64 72 107 126 
Winter Power Consumption (kW) 13 18 22 25 37 43 
Maximum Operating Power (kW) 18 26 32 38 52 64 
Maximum Operating Current (A) 34 49 61 72 99 122 
Rated hot water temperature CC 55 55 55 55 55 55 
Maximum hot water temperature CC 60 60 60 60 60 60 
Circulating water flow rate (m³/h) >11>16>20>23>33>42
Cyclic takeover specifications 1.5-inch external thread 2.5-inch flange 2.5-inch flange 2.5-inch flange 4-inch flange 4-inch flange
Water refill connection specification 1-inch external thread 1.2-inch external thread 1.2-inch external thread 1.2-inch external thread 1.5-inch external thread 1.5-inch external thread
Operating noise (dB) 75 80 80 80 85 85 
Appearance
Size
Length (mm) 1480 1800 2000 2400 2200 2200 
Width (mm) 900 1050 1050 1050 2000 2000 
Height (mm) 1650 2050 2050 2050 2050 2050 
Weight (kg)  530 700 800 850 1350 1550 
Quantity (units) 2  4 (2 units optional) 4 (2 units optional) 4 4 4 
Compressor Form Fully enclosed scroll type
Refrigerant R22 (optional R410a)
Wind turbine Quantity (units) 2 2 2 3 4 4 
Form Axial fan
Applicable Ambient Temperature Range (°C) -10~40℃

Note: 1. Rated heating test conditions: initial hot water temperature 15°C, final hot water temperature 55°C; ambient dry-bulb temperature 20°C, ambient wet-bulb temperature 15°C.

2. Winter heating test conditions: initial hot water temperature 9°C, final hot water temperature 55°C; ambient dry-bulb temperature 7°C, ambient wet-bulb temperature 6°C.

Keywords:

Heat exchanger

Welcome to leave a message or inquiry.

Our staff will contact you within 24 hours (on business days). If you require any additional services, please feel free to call our service hotline: +8618102505973